West Sussex · RH postcodes
TR19® Grease Inspection & Testing in Crawley
Our crews carry out TR19® Grease inspection & testing in Crawley and the rest of West Sussex, working overnight or on closed days so service carries on.

What does TR19® Grease inspection & testing in Crawley include?
A TR19® Grease inspection tells you how much grease is in your extract system and when it needs cleaning. We survey the route from canopy to fan, take deposit thickness tests with a wet film gauge, photograph the findings and set a cleaning interval based on your cooking hours.
Busy Crawley kitchens often run fryers and grills for long hours. That puts them in the heavy-use band, where grease builds quickly and cleaning every three months is the TR19® Grease minimum.
Food production units and central kitchens near Crawley can need cleaning more often than the TR19® Grease minimum, so we use test results to set the interval.
We start by tracing the system from the canopy to the point of discharge, then take deposit thickness tests and photos. Equipment is sheeted before any degreasing starts.
- Deposit thickness tests at set points
- Fire risk notes on access, dampers and fans
- Recommended cleaning interval by cooking hours
- Photos of each test position
| Town | Crawley, West Sussex |
|---|---|
| Postcode area | RH |
| Nearest covered town | Horsham (7 miles) |
| Guide price | Typically £150 to £350 per system, credited against a clean booked within 30 days. |
From Crawley we also cover Horsham (about 7 miles), Haywards Heath (8 miles) and Redhill (9 miles).
- Horsham about 7 miles
- Haywards Heath about 8 miles
- Redhill about 9 miles
- Leatherhead about 14 miles
- Epsom about 16 miles
- Sutton about 17 miles
Send us your postcode and opening hours and we will come back with survey dates for Crawley. More about tr19® grease inspection & testing.
TR19® Grease Inspection & Testing in Crawley: questions
Do you cover Crawley?
Yes. We provide tr19® grease inspection & testing in Crawley and across RH postcodes, as well as nearby Horsham, Haywards Heath, Redhill.
What is a deposit thickness test?
A deposit thickness test uses a wet film comb gauge pressed against the duct surface to measure the depth of grease in microns. TR19® Grease uses these readings to decide when cleaning is needed and to prove it was done.